Air changes per hour (ACH) & scrubber CFM
Negative-air machines and air scrubbers are sized by air changes per hour (ACH). The identity is ACH = CFM × 60 ÷ room volume (cu ft), so the airflow you need is required CFM = ACH × volume ÷ 60. Containment and IAQ work usually targets 4–6 ACH. These are labeled planning conventions. Use them in the air-scrubber CFM tool.
| Room volume | CFM for 4 ACH | CFM for 6 ACH | Scrubbers @ 500 CFM (6 ACH) |
|---|---|---|---|
| 1,500 cu ft | 100 CFM | 150 CFM | 1 unit |
| 2,700 cu ft | 180 CFM | 270 CFM | 1 unit |
| 4,000 cu ft | 267 CFM | 400 CFM | 1 unit |
| 8,000 cu ft | 533 CFM | 800 CFM | 2 units |
Required CFM = ACH × room volume ÷ 60; ACH = CFM × 60 ÷ volume. Containment/IAQ usually targets 4–6 ACH. Labeled planning conventions.